heating and cooling wall with integrated capillary tube mat OPTIMAT GB 15
OPTIPANEL 15 UNGELOCHT – FÜR DECKE UND WAND
Belfius Tower Brussels VIP Offices © Jaspers-Eyers Architects / Photography Nicolas Schimp

system description

Design
Clina OPTIPANEL 15 is a prefabricated gypsum board panel with an integrated capillary tube mat. The OPTIPANEL 15 are screwed onto the profiles of a substructure. On the visible side there is a seamless gypsum board ceiling or wall for the removal or supply of sensitive heat loads. The water circulates noiselessly in the capillary tube mats and regulates the room temperature to a large extent via radiation, partly also via convection.

Gypsum board panel & Capillary tube mat
The OPTIPANEL 15 consists of a 12,5 mm unperforated gypsum board panel and the Clina capillary tube mat OPTIMAT GB 15.

Length & width
Clina manufactures the OPTIPANEL 15 in the dimensions 2.000 x 625 mm or 2.000 x 1.250 mm (standard). Other, project-specific dimensions can also be delivered.

The panel thickness is 12,5 mm.

Hydraulic connection
The connections between the OPTIPANEL 15 and the connection to the supply and return lines/ceiling sub-distributors are made on site using a proven push-lock system with flexible hoses. Pipes and sub-distributors are housed in the ceiling or wall cavity. 

Of course, the ceiling or wall cavity can be used for other installations.
 

Mounting
The prefabricated OPTIPANEL 15 are screwed onto the profiles of the substructure/stud frame.

The screws are screwed in through holes drilled in the factory.

Processing
According to the common rules of drywall. Processing of inactive areas with 12,5 mm standard gypsum board panels.

Lamps & Ventilation
Openings have to be taken into account in the planning phase.

Regulation
The system can be regulated room-by-room.

Fields of application
Suitable for the modern interior design of rooms with special acoustic requirements, such as office buildings or public buildings, whether new construction or renovation.
 

structure

Aufbau UK OPTIPANEL

The prefabricated OPTIPANEL 15 are screwed onto the profiles of the substructure/stud frame. The screws are screwed in through holes drilled in the factory.

The connections between the OPTIPANEL 15 and the connection to the supply and return lines/ceiling sub-distributors are made on site using a proven push-lock system with flexible hoses. 

Pipes and sub-distributors are housed in the ceiling or wall cavity. 

Of course, the cavity can be used for other installations.

prefabricated product

In an unperforated 12,5 mm gypsum board panel, parallel slots are milled on the back at a distance of
15 mm. 

The capillaries of the OPTIMAT GB 15 capillary tube mat, consisting of a round mat distributor pipe (20 x 2,0 mm) and capillary tubes (4,3 x 0,8 mm), are inserted into these slots.

The distance between the capillary tubes (centre-to-centre distance) is 15 mm. 

The OPTIPANEL 15 is covered with a full-surface cover paper on the back.

 

to the prefabricated product OPTIPANEL 15

OPTIPANEL 15 mit KRM in GK-Decke mit ungelochter Oberfläche

advantages

Cooling and heating with one system
In most buildings, the heat requirement to be covered is so low due to the well-insulated building envelope that capillary tube mats integrated invisibly in the gypsum board ceiling or gypsum board wall not only provide excellent and silent cooling in summer, but can also be used to heat very comfortably and energy-efficient in the cold season.

High degree of prefabrication
Factory prefabrication ensures quality, function and thermal performance.

Easy retrofitting
Can be screwed onto an existing substructure. The hydraulic connection is made in the ceiling or wall cavity. 

Activation does not increase the ceiling load.

Quick and easy installation
The hydraulic connection is made using a proven push-lock system.

This design can be installed completely in the drywall work, which ensures a smooth process on the construction site.

Individual room control
The system can be regulated room-by-room.

values

HEATING CAPACITY

(ceiling) according to DIN EN 14037/5

COOLING CAPACITY

(ceiling) according to DIN EN 14240

ACOUSTICS

(ceiling) (applies only to perforated version)

92,0 W/m²
ΔT = 15 K, acitve mat surface

77,3 W/m²
ΔT = 15 K, total panel surface

74,4 W/m²
ΔT = 10 K, acitve mat surface

63,7 W/m²
ΔT = 10 K, total panel surface

for perforated version see

OPTIPANEL 18 

INSTALLATION HEIGHT:
depending on the kind of substructure
plus 12,5 mm OPTIPANEL 15

SYSTEM WEIGHT:
OPTIPANEL 15 (filled with water)
11 kg/m² plus substructure + insulation

PRESSURE STAGE:
PN 10